Fire safety inspection requirements in Germany
What a fire inspection has to cover in Germany — the instruments that impose it, and the clause each check is cited to.
1 instrument · 35 requirements · 44 checks · authoritative language: DE
Requirements below are shown in DE — the legally authoritative language in Deutschland — with an English translation beneath. The translation is a convenience and is never the requirement itself.
The instruments we cite
Wiederkehrende Prüfung der Brandschutzeinrichtungen · edition BetrSichV 2015 i.d.F. 2025; ASR A2.2 2018, 3. Änderung Mai 2025
§14 BetrSichV i. V. m. ASR A2.2, DIN 14406-4, DIN 14676, DIN 14677, DIN 14675/DIN VDE 0833, DIN EN 50172/VDE 0108-100 (2024-10), DIN EN 1838 (2025-03), DIN 18232/DIN EN 12101
What an inspection covers
ASR A1.3 (DIN 4844-2 / DIN EN ISO 7010); DIN ISO 23601:2020 — Kennzeichnung & Flucht-/Rettungsplan
Rettungswege, Notausgänge und Standorte von Brandschutzeinrichtungen müssen dauerhaft und erkennbar gekennzeichnet sein (Sicherheitszeichen nach ASR A1.3 / DIN 4844-2 / DIN EN ISO 7010); wo erforderlich sind aktuelle Flucht- und Rettungspläne nach DIN ISO 23601:2020 auszuhängen. Bundeseinheitlich.
Escape routes, emergency exits and locations of fire-protection equipment must be permanently and recognisably signed (safety signs per ASR A1.3 / DIN 4844-2 / DIN EN ISO 7010); where required, up-to-date escape and rescue plans per DIN ISO 23601:2020 must be displayed. Federal-uniform.
Checks on this requirement
- Are escape routes/exits/fire equipment correctly signed and (where required) current escape & rescue plans per DIN ISO 23601 displayed?
ASR A2.2 (Ausgabe 2018, 3. Änd. Mai 2025 §7.1); DGUV I 205-003; vfdb 12-09/01; DGUV I 205-023 — Brandschutzbeauftragte(r) & Brandschutzhelfer
Sofern durch Baurecht (Sonderbau/LBO) oder die Gefährdungsbeurteilung ausgelöst, ist ein Brandschutzbeauftragter zu bestellen (Aufgaben/Qualifikation nach DGUV I 205-003 / vfdb 12-09/01; ASR A2.2 §7.1 nach 3. Änderung Mai 2025). Zusätzlich ist eine ausreichende Zahl ausgebildeter Brandschutzhelfer (in der Regel ≈5 % der Beschäftigten, ASR A2.2 / DGUV I 205-023) zu benennen. Bundeseinheitlich; baurechtliche Auslösung landesrechtlich (Sonderbau).
Where triggered by building law (Sonderbau/LBO) or the risk assessment, a fire-protection officer must be appointed (tasks/qualification per DGUV I 205-003 / vfdb 12-09/01; ASR A2.2 §7.1 after the May 2025 3rd amendment). In addition, a sufficient number of trained fire-safety assistants (typically ≈5% of staff, ASR A2.2 / DGUV I 205-023) must be designated. Federal-uniform; the building-law trigger is state-dependent (Sonderbau).
Checks on this requirement
- Is a fire-protection officer appointed and qualified where required (Sonderbau/LBO or risk assessment) (DGUV I 205-003 / vfdb 12-09/01)?
- Is a sufficient number of trained fire-safety assistants designated (typically ≈5% of staff, ASR A2.2 / DGUV I 205-023)?
ArbSchG §12; ASR A2.2; DGUV — Unterweisung & Räumungsübung
Beschäftigte sind bei Einstellung und wiederkehrend (in der Regel jährlich) zum Brandschutz und Verhalten im Brandfall zu unterweisen; Räumungs-/Evakuierungsübungen sind durchzuführen und zu dokumentieren. Bundeseinheitlich (ArbSchG §12).
Staff must be instructed on fire safety and behaviour in a fire on hiring and periodically (usually annually); evacuation drills must be carried out and documented. Federal-uniform (ArbSchG §12).
Checks on this requirement
- Have staff received fire-safety instruction on time and has an evacuation drill been carried out and documented?
ArbSchG §5/§6; TRGS 800 — Gefährdungsbeurteilung Brandschutz
Für die Arbeitsstätte ist eine Gefährdungsbeurteilung mit Bewertung der Brandgefährdung (normal/erhöht/hoch nach TRGS 800) durchzuführen und nach ArbSchG §6 zu dokumentieren; daraus leiten sich technische, organisatorische und personenbezogene Maßnahmen (u. a. Löschmittel-bemessung nach ASR A2.2) ab. Bundeseinheitlich (Arbeitsschutzrecht des Bundes).
A workplace risk assessment must evaluate the fire hazard (normal/increased/high per TRGS 800) and be documented under ArbSchG §6; it drives technical, organisational and personal measures (incl. extinguisher sizing per ASR A2.2). Federal-uniform (federal occupational-safety law).
Checks on this requirement
- Is there a current, documented fire-risk assessment (fire hazard classified per TRGS 800) and is it updated after changes?
ArbSchG §5; MVStättV (Belegung) — Personen & besonders gefährdete Personen
Die maßgebliche Personenzahl (Beschäftigte, Besucher, Gesamt) je Bereich ist zu ermitteln und auf die Kapazität der Rettungswege zu beziehen. Besonders gefährdete oder auf Hilfe angewiesene Personen (mobilitäts-/sinneseingeschränkte Personen, Ortsunkundige, Allein-/Nachtarbeitende, schlafende Nutzer) sind zu ermitteln und ihre Evakuierung ist zu regeln.
The relevant number of persons (staff, visitors, total) per area must be established and related to escape-route capacity. Persons especially at risk or needing assistance (mobility/sensory impaired, unfamiliar, lone/night workers, sleeping occupants) must be identified and their evacuation arranged.
Checks on this requirement
- Have persons especially at risk been identified and their evacuation arranged (e.g. evacuation assistants, accessible escape route)?
- Is the relevant number of persons per area established and reconciled with escape-route capacity?
ArbSchG §5; organisatorischer Brandschutz — Brandstiftung/Zugangssicherung
Die Gefahr vorsätzlicher Brandstiftung ist zu mindern: gesicherter Zugang, keine frei zugänglichen Brandlasten an der Fassade/an Zufahrten, kontrollierter Zutritt. Organisatorische Maßnahme (bundeseinheitlich).
The risk of deliberate ignition (arson) must be reduced: secured access, no freely accessible fuel loads against the façade/at access routes, controlled entry. Organisational measure (federal-uniform).
Checks on this requirement
- Are measures against arson adequate (access secured, no fuel loads against the façade/waste at the wall)?
ArbSchG §6; Gefährdungsbeurteilung — Dokumentation, Mängelbewertung & Maßnahmenplan
Festgestellte Mängel sind zu bewerten und in einen priorisierten, terminierten Maßnahmenplan (technisch/organisatorisch/personenbezogen, mit Verantwortlichem und Frist) zu überführen; Ergebnis und Wirksamkeitskontrolle sind nach ArbSchG §6 zu dokumentieren und mit Wiedervorlage-/Prüftermin fortzuschreiben. Bundeseinheitlich.
Identified deficiencies must be evaluated and turned into a prioritised, time-bound action plan (technical/organisational/personal, with owner and deadline); the result and effectiveness check must be documented under ArbSchG §6 and kept current with a review date. Federal-uniform.
Checks on this requirement
- Has each deficiency been evaluated and documented with a prioritised, time-bound action (owner, deadline, effectiveness check)?
ArbStättV Anh. 2.3 / ASR A2.3 — Notausgänge / Türen im Fluchtweg
Türen im Verlauf von Fluchtwegen und Notausgänge müssen sich jederzeit ohne fremde Hilfsmittel (ohne Schlüssel) in Fluchtrichtung öffnen lassen; erforderliche Panik-/Notausgangsverschlüsse müssen funktionieren. Bundeseinheitlich (ASR A2.3).
Doors along escape routes and emergency exits must open at any time without aids (without a key) in the direction of escape; required panic/emergency-exit hardware must function. Federal-uniform (ASR A2.3).
Checks on this requirement
- Can emergency exits/escape doors be opened at any time without a key in the escape direction, and does required panic/emergency hardware work?
ArbStättV; ASR A1.3 — Rauchverbot/-regelung
Das Rauchen muss geregelt sein (Rauchverbote, ausgewiesene Bereiche, Kennzeichnung, sichere Ascheentsorgung); Zündquelle Rauchen darf nicht mit Brandlasten zusammentreffen. Organisatorische Maßnahme im Rahmen des Arbeitsschutzes (bundeseinheitlich).
Smoking must be controlled (bans, designated areas, signage, safe ash disposal); the smoking ignition source must not meet fuel loads. Organisational measure under occupational safety (federal-uniform).
Checks on this requirement
- Is a smoking policy implemented (bans/areas signed, safe ash disposal) and observed?
ArbStättV; ASR A2.2 — Brandlasten, Lagerung, Ordnung
Brennbare Stoffe und Abfälle sind zu begrenzen und von Zündquellen sowie aus Flucht- und Rettungswegen fernzuhalten; Ordnung und Sauberkeit sind zu wahren. Bundeseinheitlich (Arbeitsschutz).
Combustible materials and waste must be limited and kept away from ignition sources and escape routes; good housekeeping must be maintained. Federal-uniform (occupational safety).
Checks on this requirement
- Are combustibles/waste limited and kept away from ignition sources and escape routes (good housekeeping)?
DGUV / vfdb — Heißarbeiten (Erlaubnisschein)
Feuergefährliche Arbeiten (Schweißen, Trennen, Löten) durch Eigen- oder Fremdpersonal sind über einen Erlaubnisschein zu steuern (Freigabe, Brandwache, Nachkontrolle, Bereitstellung von Löschmitteln). Organisatorische Maßnahme (bundeseinheitlich).
Hot works (welding, cutting, soldering) by own or contractor staff must be controlled by a hot-work permit (authorisation, fire watch, post-work check, extinguishers provided). Organisational measure (federal-uniform).
Checks on this requirement
- Are hot works controlled by a permit (authorisation, fire watch, post-work check, extinguishers ready)?
DGUV Vorschrift 3; DIN VDE 0105-100 / 0701-0702 — elektrische Anlagen & Betriebsmittel
Ortsfeste und ortsveränderliche elektrische Anlagen und Betriebsmittel müssen in sicherem Zustand sein (keine Beschädigung, Überlast, Überhitzung) und wiederkehrend durch eine Elektrofachkraft geprüft werden (DGUV Vorschrift 3 i. V. m. DIN VDE 0105-100 / 0701-0702). Prüffristen sind gefährdungsbezogen (ortsveränderliche Geräte je nach Umgebung ~6–24 Monate). Bundeseinheitlich (autonome Unfallverhütungsvorschrift der Berufsgenossenschaften).
Fixed and portable electrical installations and equipment must be in a safe condition (no damage, overload, overheating) and periodically tested by a qualified electrician (DGUV V3 with DIN VDE 0105-100 / 0701-0702). Intervals are risk-based (portable equipment ~6–24 months by environment). Federal-uniform (autonomous accident-prevention regulation of the BGs).
Checks on this requirement
- Are electrical installations/equipment undamaged and free of overload/overheating signs (no cable damage, no daisy-chained adaptors)?
- Have electrical installations and equipment been tested on time per DGUV V3 and is the test recorded?
DIN 14096:2014-05 — Brandschutzordnung (Teil A/B/C)
Eine Brandschutzordnung nach DIN 14096:2014-05 muss vorhanden und aktuell sein: Teil A (Aushang für alle), Teil B (Personen ohne besondere Aufgaben), Teil C (Personen mit besonderen Aufgaben). Überprüfung mindestens alle 2 Jahre (Empfehlung der Norm/DGUV-Praxis). Bundeseinheitlich; Interval weicht von UK-Vorgaben ab (Cross-Jurisdiction-Interval-Engine beachten).
A fire-safety regulation per DIN 14096:2014-05 must exist and be current: Part A (public notice for all), Part B (persons without special duties), Part C (persons with special duties). Review at least every 2 years (norm/DGUV-practice recommendation). Federal-uniform; the interval differs from UK requirements (feed the cross-jurisdiction interval engine).
Checks on this requirement
- Is a current fire-safety regulation per DIN 14096 in place (Part A displayed, Parts B/C prepared) and reviewed within the last 2 years?
DIN 14406-4; ASR A2.2; §14 BetrSichV — tragbare Feuerlöscher
Tragbare Feuerlöscher müssen vorhanden, gut sichtbar, gekennzeichnet, frei zugänglich und betriebsbereit sein. Wiederkehrende Prüfung durch einen Sachkundigen mindestens alle 2 Jahre (DIN 14406-4); Bereitstellung/Bemessung nach Löschmitteleinheiten gemäß ASR A2.2; Prüfung als Arbeitsmittel nach §14 BetrSichV (innere Prüfung 5 Jahre / Festigkeitsprüfung 10 Jahre je nach Bauart). Bundeseinheitlich.
Portable fire extinguishers must be present, clearly visible, signed, accessible and operational. Recurring inspection by a competent person at least every 2 years (DIN 14406-4); provision sized by extinguishing-agent units per ASR A2.2; tested as work equipment under §14 BetrSichV (internal test 5 years / strength test 10 years depending on type). Federal-uniform.
Checks on this requirement
- Have the extinguishers been inspected on time (every 2 years, valid inspection tag) and are they operational (gauge in the green zone)?
- Are extinguishers present, clearly visible, marked with the fire-safety sign and freely accessible?
DIN 14462:2023-07; DIN EN 671-3 — Wandhydranten / Löschwasseranlagen
Vorhandene Wandhydranten und Löschwasseranlagen (Steigleitungen, Über-/Unterflurhydranten) müssen zugänglich, funktionsfähig und wiederkehrend geprüft sein — mindestens jährliche Wartung durch eine Fachfirma nach DIN 14462:2023-07 i. V. m. DIN EN 671-3; monatliche Sichtkontrolle der Zugänglichkeit durch den Betreiber. Erfordernis ist objekt-/landesrechtlich (Sonderbau/Löschwasserbedarf).
Existing wall hydrants and firefighting water systems (rising mains, over/underground hydrants) must be accessible, functional and periodically tested — at least annual servicing by a specialist firm per DIN 14462:2023-07 with DIN EN 671-3; monthly visual accessibility check by the operator. The requirement is object/state-dependent (Sonderbau / firefighting-water need).
Checks on this requirement
- Are wall hydrants/firefighting-water systems accessible, undamaged and serviced on time (annually)?
DIN 14675-1:2020 / -2:2020; DIN VDE 0833-1:2014-10 / -2:2022-06 — Brandmeldeanlage (BMA)
Eine erforderliche/vorhandene Brandmeldeanlage (BMA) muss betriebsbereit und instand gehalten sein; Melder dürfen nicht verdeckt/verstellt sein. Inspektion vierteljährlich, Wartung jährlich durch eine Fachfirma (DIN 14675-1 Aufbau/Betrieb, DIN 14675-2 Fachfirma; DIN VDE 0833 Betrieb); Begehungen/Störungen im Betriebsbuch. Notwendigkeit und Aufschaltung zur Feuerwehr sind objekt-/landesrechtlich (Sonderbau) bestimmt.
A required/existing fire-detection & alarm system (BMA) must be operational and maintained; detectors must not be covered/obstructed. Inspection quarterly, servicing annually by a specialist firm (DIN 14675-1 build/operation, DIN 14675-2 specialist firm; DIN VDE 0833 operation); inspections/faults in the logbook. The need for and fire-brigade transmission are determined per object/state law (Sonderbau).
Checks on this requirement
- Has the BMA been inspected on time (quarterly inspection, annual servicing by a specialist firm) and is the logbook kept?
- Is the BMA in operation (no standing fault/disablement messages) and are detectors uncovered and unobstructed?
DIN 14676; LBO (Rauchwarnmelderpflicht) — Rauchwarnmelder in Wohnungen
In Schlafräumen, Kinderzimmern und als Rettungsweg dienenden Fluren von Wohnungen müssen Rauchwarnmelder vorhanden und betriebsbereit sein; Inspektion/Wartung jährlich nach DIN 14676. Umfang und Pflichtträger (Eigentümer/Mieter) sind landesrechtlich in der jeweiligen LBO geregelt — in allen 16 Bundesländern eingeführt, Details variieren je Bundesland.
Smoke alarms must be present and operational in bedrooms, children's rooms and hallways serving as escape routes in dwellings; annual inspection/maintenance per DIN 14676. Scope and the responsible party (owner/tenant) are set by the respective state LBO — adopted in all 16 states, details vary.
Checks on this requirement
- Are smoke alarms present in the required rooms and operational (test button passes, no low-battery warning)?
DIN 14677-1:2018; MBO §35 (via LBO) — Feuer-/Rauchschutzabschlüsse & Feststellanlagen
Feuer- und Rauchschutzabschlüsse (Brandschutztüren) müssen selbstschließend, unbeschädigt und funktionsfähig sein und dürfen nicht unzulässig festgestellt (verkeilt) werden. Elektrische Feststellanlagen sind jährlich durch eine befähigte Person instand zu halten (DIN 14677-1). Die konkrete bauliche Anforderung ergibt sich aus der LBO (MBO §35 als Muster).
Fire and smoke barriers (fire doors) must be self-closing, undamaged and functional and must not be improperly held open (wedged). Electric hold-open devices must be maintained annually by a qualified person (DIN 14677-1). The actual structural requirement derives from the LBO (MBO §35 as model).
Checks on this requirement
- Are the doors undamaged and the hold-open system demonstrably tested (annually, DIN 14677-1)?
- Do the fire/smoke doors self-close fully into the frame and are they not wedged or propped open?
DIN 18232-2:2007 / -5:2012; DIN EN 12101 — Rauch- und Wärmeabzug (RWA)
Vorhandene/erforderliche Rauch- und Wärmeabzugsanlagen (natürliche NRA / maschinelle RWA) müssen funktionsfähig, ausgelöst-fähig und frei sein; Auslöse-/Bedienstellen dürfen nicht verstellt sein. Funktionsprüfung in der Regel jährlich (DIN 18232 / DIN EN 12101). Erfordernis ist objekt-/landesrechtlich (Sonderbau).
Existing/required smoke & heat exhaust systems (natural NRA / mechanical RWA) must be functional, able to trigger and unobstructed; trigger/control points must not be blocked. Function test typically annual (DIN 18232 / DIN EN 12101). The requirement is object/state-dependent (Sonderbau).
Checks on this requirement
- Are RWA/NRA systems functional, clear and tested on time (annually), and are trigger/control points clear?
DIN EN 12845; DIN 14489; VdS CEA 4001 / VdS 2093; DIN EN 15004 — ortsfeste Löschanlagen (Sprinkler-/Gaslöschanlagen)
Vorhandene/erforderliche ortsfeste Löschanlagen (Sprinkler-, Sprühwasser-, Gas- oder Objektlöschanlagen) müssen betriebsbereit, unverstellt und wiederkehrend geprüft sein: Sprinklerdüsen frei (Mindestabstand zum Lagergut), Absperrarmaturen in Betriebsstellung, Löschwasser-/Löschmittelvorrat und Pumpen/Druck bereit, keine anstehende Störung. Instandhaltung durch eine Fachfirma nach DIN 14489 bzw. VdS-Richtlinien (Sprinkler VdS CEA 4001; Gaslöschanlagen DIN EN 15004 / VdS 2093) mit vierteljährlicher/jährlicher Prüfung. Erfordernis ist objekt-/landesrechtlich (Sonderbau, Brandschutzkonzept, Sachversicherer-Auflage).
Existing/required fixed extinguishing systems (sprinkler, water-spray, gas or local-application) must be operational, unobstructed and periodically tested: sprinkler heads clear (minimum clearance to stored goods), valves in operating position, water/agent supply and pumps/pressure ready, no standing fault. Servicing by a specialist firm per DIN 14489 or VdS rules (sprinkler VdS CEA 4001; gas systems DIN EN 15004 / VdS 2093) with quarterly/annual testing. The requirement is object/state-dependent (Sonderbau, fire-protection concept, property-insurer condition).
Checks on this requirement
- Has the fixed extinguishing system been inspected/serviced on time by a specialist firm (DIN 14489 / VdS) and is the agent/water supply secured?
- Is the fixed extinguishing system in operation (valves in operating position, no standing fault) and are sprinklers/nozzles clear and unobstructed (minimum clearance to stored goods maintained)?
DIN EN 1838:2025-03; DIN EN 50172 / DIN VDE 0108-100:2024-10 — Sicherheitsbeleuchtung
Die Sicherheits-/Notbeleuchtung muss bei Ausfall der Allgemeinbeleuchtung Rettungswege und Sicherheitszeichen ausreichend beleuchten (Beleuchtungsstärken nach DIN EN 1838:2025-03). Prüfung: tägliche Sichtkontrolle, monatliche Funktionsprüfung, jährliche Prüfung der Bemessungsbetriebsdauer; Erstprüfung und Prüfbuch nach DIN EN 50172 / DIN VDE 0108-100:2024-10. Bundeseinheitlich.
Safety/emergency lighting must adequately illuminate escape routes and safety signs on loss of general lighting (illuminance per DIN EN 1838:2025-03). Testing: daily visual check, monthly function test, annual rated-duration test; initial verification and logbook per DIN EN 50172 / DIN VDE 0108-100:2024-10. Federal-uniform.
Checks on this requirement
- Does the emergency lighting switch on when mains power fails and adequately illuminate escape routes and exit signs?
- Have the monthly function test and the annual rated-duration test been performed and recorded in the logbook?
DIN EN 62305 (VDE 0185-305), 2011-10 — Blitzschutzanlage
Eine erforderliche/vorhandene Blitzschutzanlage (äußerer/innerer Blitzschutz) muss vollständig, unbeschädigt und wiederkehrend geprüft sein (DIN EN 62305 / VDE 0185-305). Prüfintervall abhängig von Blitzschutzklasse und Umgebung (nationale Beiblätter). Erfordernis ist objekt-/landesrechtlich.
A required/existing lightning-protection system (external/internal LPS) must be complete, undamaged and periodically tested (DIN EN 62305 / VDE 0185-305). The interval depends on the protection class and environment (national supplements). The requirement is object/state-dependent.
Checks on this requirement
- Is a required lightning-protection system present, undamaged and tested on time (per protection class)?
DIN EN 81-72 (Feuerwehraufzüge); DIN EN 81-73 (Brandfallsteuerung); MHHR (via Land); BetrSichV Anh. 2 Abschn. 2 — Aufzüge im Brandfall
Aufzüge müssen im Brandfall sicher beherrscht werden: Personenaufzüge mit Brandfallsteuerung (Evakuierungssteuerung) müssen bei Auslösung der BMA in die Bestimmungshaltestelle fahren, dort Türen öffnen und außer Betrieb gehen (DIN EN 81-73); ein erforderlicher Feuerwehraufzug (i. d. R. Hochhäuser > 22 m nach MHHR/LBO) muss betriebsbereit sein und einen rauchfreien, sicheren Vorraum haben (DIN EN 81-72). Normale Aufzüge dürfen im Brandfall nicht benutzt werden (Kennzeichnung). Aufzüge sind zudem überwachungsbedürftige Anlagen (ZÜS-Prüfung nach BetrSichV Anh. 2 Abschn. 2). Erfordernis Feuerwehraufzug ist landesrechtlich/objektabhängig.
Lifts must be safely managed in a fire: passenger lifts with fire-recall (evacuation) control must, on BMA activation, travel to the designated floor, open doors and go out of service (DIN EN 81-73); a required firefighters lift (typically high-rises >22 m per MHHR/LBO) must be operational with a smoke-free, safe lobby (DIN EN 81-72). Ordinary lifts must not be used in a fire (signage). Lifts are also monitored equipment (ZÜS inspection per BetrSichV Annex 2 §2). The firefighters-lift requirement is state/object-dependent.
Checks on this requirement
- Do fire-recall lifts travel to the designated floor and go out of service on BMA activation, is a required firefighters lift operational, and is 'do not use lifts in a fire' signed for ordinary lifts?
DIN VDE 0100-560/-718; DIN VDE 0108-100:2024-10; DIN 6280 — Sicherheitsstromversorgung / Notstrom (SV/BSV)
Sofern für sicherheitstechnische Anlagen erforderlich (z. B. Versammlungsstätten, Hochhäuser, Verkaufsstätten — MVStättV/MHHR via LBO), muss eine Sicherheitsstromversorgung (Ersatzstromquelle: Batterieanlage/Zentralbatterie oder Stromerzeugungsaggregat) vorhanden, ausreichend bemessen und betriebsbereit sein und die angeschlossenen Sicherheitseinrichtungen (Sicherheitsbeleuchtung, BMA, RWA, Feuerwehraufzug, Druckbelüftung, ggf. Löschwasserpumpen) im geforderten Umschalt-/Nennbetriebszeitraum versorgen. Wiederkehrende Prüfung/Probelauf (Kraftstoffvorrat, Umschaltung, Batteriekapazität) nach DIN VDE 0108-100 / DIN 6280 und Herstellerangaben; Bemessung/Erfordernis landesrechtlich/objektabhängig.
Where required for safety installations (e.g. assembly venues, high-rises, retail — MVStättV/MHHR via LBO), a safety power supply (secondary source: central-battery system or generator set) must exist, be adequately sized and operational and feed the connected safety equipment (emergency lighting, BMA, smoke exhaust, firefighters lift, pressurisation, firefighting pumps) for the required changeover/rated duration. Recurring test/trial run (fuel supply, changeover, battery capacity) per DIN VDE 0108-100 / DIN 6280 and manufacturer instructions; sizing/need is state/object-dependent.
Checks on this requirement
- Is a safety power supply (central battery/generator) present, operational, adequately sized and tested on time by trial run (changeover, fuel/battery) where required?
GefStoffV; TRGS 800; BetrSichV — Gefahrstoffe / Ex-Bereiche
Brennbare/hochentzündliche Gefahrstoffe müssen ermittelt, korrekt gelagert und begrenzt sein; explosionsfähige Atmosphären sind zu beurteilen (Explosionsschutzdokument nach GefStoffV/BetrSichV). Bundeseinheitlich (Gefahrstoffrecht des Bundes).
Flammable/highly flammable hazardous substances must be identified, correctly stored and limited; explosive atmospheres must be assessed (explosion-protection document per GefStoffV/BetrSichV). Federal-uniform (federal hazardous-substances law).
Checks on this requirement
- Are hazardous substances identified, correctly and quantity-limited stored, and (where explosive) assessed in the explosion-protection document?
Land-Prüfverordnung (SPrüfV/PrüfVO); LBO — Brandverhütungsschau & wiederkehrende Prüfung
Wiederkehrende Prüfungen sicherheitstechnischer Anlagen durch Prüfsachverständige/-sachkundige und — soweit im Land vorgesehen — die behördliche Brandverhütungsschau müssen fristgerecht durchgeführt und die Prüfberichte vorgelegt sein. Pflicht, Intervalle, Prüferqualifikation und ob eine Brandverhütungsschau überhaupt stattfindet, sind landesrechtlich (LBO + Prüf-/Brandschauverordnung) und weichen zwischen den Ländern ab (z. B. NRW/Sachsen mit BVS; Hamburg/Berlin ⚠️ eher Prüfsachverständigenmodell — je Land verifizieren).
Recurring inspections of safety-related installations by approved/qualified inspectors and — where the state provides for it — the official fire-prevention inspection (Brandverhütungsschau) must be carried out on time and the reports available. The duty, intervals, inspector qualification and whether a Brandverhütungsschau exists at all are set by state law (LBO + inspection ordinance) and differ by state (e.g. NRW/Saxony retain the BVS; Hamburg/Berlin ⚠️ lean on the approved-inspector model — verify per state).
Checks on this requirement
- Have the state-required recurring inspections / the fire-prevention inspection been carried out on time and are the reports available?
M-LüAR (Muster-Lüftungsanlagen-Richtlinie, via LTB des Landes); DIN EN 15650; DIN 18017-3 — Brandschutzklappen & Lüftungsanlagen
Brandschutzklappen und brandschutztechnische Einrichtungen raumlufttechnischer Anlagen (Lüftungsleitungen, die Brandabschnitte queren) müssen funktionsfähig, unbeschädigt und zugänglich sein und selbsttätig schließen. Wiederkehrende Funktionsprüfung — in der Regel halbjährlich — nach der Muster-Lüftungsanlagen-Richtlinie (M-LüAR, bauaufsichtlich eingeführt über die LTB/Verwaltungsvorschrift des Landes) i. V. m. DIN EN 15650 (Produkt) und den Herstellerangaben. Abweichende Prüfcadence (6-monatlich) für die Cross-Jurisdiction-Interval-Engine beachten.
Fire dampers and fire-protection features of ventilation (HVAC) systems (ducts crossing fire compartments) must be functional, undamaged and accessible and must self-close. Recurring function test — typically every six months — per the model ventilation-systems directive (M-LüAR, adopted via the state's building-code technical rules) with DIN EN 15650 (product) and manufacturer instructions. Note the divergent (6-monthly) cadence for the cross-jurisdiction interval engine.
Checks on this requirement
- Are fire dampers in ventilation ducts accessible, undamaged and function-tested on time (typically six-monthly), with self-closing documented?
MBO §2 (Gebäudeklassen, Sonderbau) — via LBO des Landes
Bauart, Grundriss, Geschosszahl, Flächen und Nutzung des Gebäudes sind zu erfassen und der Gebäudeklasse (GK 1–5 nach MBO §2, umgesetzt in der jeweiligen Landesbauordnung) sowie ggf. der Sonderbau-Eigenschaft (§2 Abs. 4 — z. B. Versammlungsstätte, Hochhaus, Industriebau, Beherbergung, Krankenhaus, Verkaufsstätte) zuzuordnen. Die konkreten Schwellen und Pflichten ergeben sich landesrechtlich aus der LBO des Bundeslands; die MBO ist nur Muster.
The construction, layout, number of storeys, floor areas and use of the building must be recorded and mapped to its building class (GK 1–5 per MBO §2, as transposed by the relevant state building code) and, where applicable, its special-building (Sonderbau) status (§2(4) — e.g. assembly venue, high-rise, industrial, accommodation, hospital, retail). The actual thresholds and duties derive from the specific state's LBO; the MBO is only a model.
Checks on this requirement
- Do the recorded construction, building class (GK 1–5) and use match the building as found, and has it been checked whether it is a special building (assembly/high-rise/industrial/accommodation/hospital/retail)?
MBO §33 (via LBO); ArbStättV Anh. 2.3 / ASR A2.3 — Flucht- und Rettungswege
Flucht- und Rettungswege müssen ständig frei gehalten, in nutzbarer Breite verfügbar und in Anzahl/Länge ausreichend sein. Die baulichen Anforderungen (Anzahl, Länge, Führung) ergeben sich aus MBO §33, umgesetzt in der LBO des Landes; der betriebliche Freihaltungsgrundsatz aus ArbStättV Anh. 2.3 / ASR A2.3 (bundeseinheitlich).
Escape and rescue routes must be kept clear at all times, available at usable width, and adequate in number/length. The structural requirements (number, length, routing) derive from MBO §33 as transposed into the state LBO; the operational keep-clear principle from ArbStättV Annex 2.3 / ASR A2.3 (federal-uniform).
Checks on this requirement
- Are escape and rescue routes free of obstructions/storage and available at full usable width?
MBO §5 (via LBO) / Muster-Richtlinie Flächen für die Feuerwehr; DIN 14095; DIN 14675 (Laufkarten) — Feuerwehrzufahrten, Aufstellflächen & Feuerwehrpläne
Zu- und Durchfahrten, Aufstell- und Bewegungsflächen für die Feuerwehr müssen vorhanden, gekennzeichnet und ständig freigehalten sein (MBO §5, umgesetzt in der LBO / Muster-Richtlinie über Flächen für die Feuerwehr — landesrechtlich). Erforderliche Feuerwehrpläne nach DIN 14095 (und, bei BMA, Feuerwehr-Laufkarten nach DIN 14675) müssen vorhanden, aktuell und mit der Feuerwehr abgestimmt sowie am Feuerwehr-/Zentralenstandort hinterlegt sein.
Fire-brigade access roads and hardstanding/setup areas must exist, be marked and be kept clear at all times (MBO §5 as transposed into the LBO / model directive on areas for the fire brigade — state law). Required fire-brigade plans per DIN 14095 (and, where a BMA exists, fire-brigade route cards per DIN 14675) must be present, current, agreed with the fire brigade and deposited at the brigade/panel location.
Checks on this requirement
- Are fire-brigade access roads and setup/movement areas present, marked and free of obstructions (no parking/storage)?
- Are current fire-brigade plans per DIN 14095 (and, where a BMA exists, route cards per DIN 14675) available, agreed with the fire brigade and correctly deposited?
MBO §66 (Brandschutznachweis) — via LBO; Brandschutzkonzept bei Sonderbau
Für die bauliche Anlage muss der erforderliche Brandschutznachweis (bautechnischer Nachweis nach MBO §66, umgesetzt in der LBO) vorliegen; bei Sonderbauten ist ein vollständiges Brandschutzkonzept erforderlich. Umsetzung, Prüfpflicht und die Gebäudeklasse, ab der eine unabhängige Prüfung (Prüfsachverständiger) verlangt wird, sind landesrechtlich geregelt und weichen zwischen den Ländern ab.
The required fire-protection verification (Brandschutznachweis per MBO §66, as transposed into the LBO) must exist for the structure; special buildings require a full fire-protection concept (Brandschutzkonzept). Implementation, the checking duty and the building class at which independent verification is required are set by state law and differ between states.
Checks on this requirement
- Does the required fire-protection verification — or, for special buildings, a fire-protection concept — exist, and does the as-built match the approved verification/concept?
MBO §§27–41 (via LBO); DIN 4102 / EN 13501 — Brandabschnitte, Brandwände, Abschottungen
Brandabschnitte, Brandwände, Decken und die Abschottung von Leitungs-/Lüftungsdurchführungen müssen intakt und ohne unverschlossene Durchbrüche sein; verwendete Baustoffe/Bauteile müssen der geforderten Klasse entsprechen (national DIN 4102 A/B bzw. F30–F180 UND/ODER harmonisiert Euroclass EN 13501 A1–F / REI — im Einzelfall angeben, welche Klasse zitiert wird). Bauliche Anforderung landesrechtlich (MBO §§27–41 als Muster).
Fire compartments, fire walls, floors and the sealing of cable/duct penetrations must be intact and free of unsealed breaches; materials/components must meet the required class (national DIN 4102 A/B or F30–F180 AND/OR harmonised Euroclass EN 13501 A1–F / REI — state which class is cited). Structural requirement per state law (MBO §§27–41 as model).
Checks on this requirement
- Are fire compartments/walls/floors intact and cable/duct penetrations properly sealed (no open breaches)?
MFeuV — via Land-FeuVO; Schornsteinfeger — Feuerungsanlagen/Heizung
Feuerungsanlagen, Abgasanlagen und Brennstofflagerung müssen instand gehalten, ausreichend abgestanden von Brennbarem und wiederkehrend überprüft/gekehrt sein (Land-Feuerungsverordnung auf Basis der MFeuV; Schornsteinfeger-Regime). Anforderungen und Fristen sind landesrechtlich.
Combustion installations, flue systems and fuel storage must be maintained, adequately clear of combustibles and periodically inspected/swept (state Feuerungsverordnung based on the MFeuV; chimney-sweep regime). Requirements and intervals are set by state law.
Checks on this requirement
- Are heating/combustion installations maintained, clear of combustibles and periodically inspected/swept (chimney sweep)?
Objekt-/Gebäudefunkanlagen für die Feuerwehr (BOS-Digitalfunk) — landesrechtlich/örtliche Brandschutzdienststelle; TR BOS / DIN VDE 0800-x
Wo bauaufsichtlich oder von der örtlichen Brandschutzdienststelle gefordert (z. B. ausgedehnte Gebäude, Tiefgaragen, unterirdische Anlagen mit unzureichender BOS-Funkversorgung), muss eine Gebäude-/Objektfunkanlage für den Digitalfunk der Feuerwehr (BOS) vorhanden, betriebsbereit und wiederkehrend geprüft sein (Funkversorgung/Feldstärke, Notstrom, Bedienstelle für die Feuerwehr). Erfordernis, Technik und Prüffristen sind örtlich/landesrechtlich geregelt (Objektfunk-Richtlinie des Landes/der Feuerwehr, TR BOS) und weichen ab.
Where required by the building authority or the local fire-brigade office (e.g. extensive buildings, underground car parks, subsurface facilities with insufficient BOS radio coverage), an in-building fire-brigade radio (BOS digital-radio) system must be present, operational and periodically tested (coverage/field strength, standby power, brigade control point). The need, technology and test intervals are set locally/by state law (state/brigade in-building-radio directive, TR BOS) and vary.
Checks on this requirement
- Where required, is an in-building fire-brigade (BOS) radio system present, operational (coverage/standby power) and tested on time?
§14 BetrSichV; DIN-Instandhaltungsnormen — Prüf- & Wartungsregime / Prüfbuch
Alle Brandschutzeinrichtungen und sicherheitsrelevanten Anlagen müssen einem geeigneten Instandhaltungs- und Prüfregime unterliegen und in betriebsbereitem Zustand gehalten werden; Prüfungen sind mit Prüf-/Betriebsbuch nachvollziehbar zu dokumentieren (§14 BetrSichV i. V. m. den jeweiligen DIN-Instandhaltungsnormen). Bundeseinheitlich.
All fire-protection equipment and safety-relevant systems must be subject to a suitable maintenance and testing regime and kept operational; tests must be traceably documented in a test/operations logbook (§14 BetrSichV with the relevant DIN maintenance standards). Federal-uniform.
Checks on this requirement
- Are all fire-protection systems maintained/tested on time and is a current test/operations logbook kept?
FireCite is in beta: all 33 jurisdictions are expert-verified and shown as preview, not yet legally authoritative for compliance use.
FireCite summarises published law and standards; it is not legal advice and not a substitute for a competent fire risk assessor or the authority having jurisdiction. Regulation changes: every citation carries the edition it was checked against.