What a fire inspection has to cover in Norway — the instruments that impose it, and the clause each check is cited to.
1 instrument · 16 requirements · 19 checks · authoritative language: NB
Requirements below are shown in NB — the legally authoritative language in Norge — with an English translation beneath. The translation is a convenience and is never the requirement itself.
The instruments we cite
Brann- og eksplosjonsvernloven LOV-2002-06-14-20 (gjeldende: alminnelig aktsomhetsplikt 5 §, eierens forebyggende sikringstiltak og vedlikeh · edition Brann- og eksplosjonsvernloven (LOV-2002-06-14-20), gjeldende med endringer; forskrift om brannforebygging (FOR-2015-12-17-1710), i kraft 1.1.2016; byggteknisk forskrift TEK17 (FOR-2017-06-19-840); NS/NS-EN standarder i gjeldende utgaver (NS 3910:2020, NS 3960:2019, NS 3926-1:2017, NS-EN 3, NS-EN 671, NS-EN 1838:2024, NS-EN 12845, NS-EN 12101, NS-EN 54, EN 13501)
What an inspection covers
Brann- og eksplosjonsvernloven (LOV-2002-06-14-20) § 13 (særskilte brannobjekter) og § 11 (brannvesenets oppgaver); forskrift om brannforebygging (FOR-2015-12-17-1710) § 9 (eierens systematiske sikkerhetsarbeid) og § 18 (risikobasert tilsyn)
LOV: Kommunen skal føre tilsyn med særskilte brannobjekter, dvs. byggverk, områder og virksomheter der brann kan medføre tap av mange liv eller store skader på helse, miljø eller materielle verdier. For slike objekter skal eier og virksomhet ha organisert brannsikkerheten gjennom systematisk sikkerhetsarbeid med en ansvarlig, og avvik som påvises ved branntilsynet skal lukkes innen fristen. Rettsgrunnlag: særskilte brannobjekter og kommunens tilsyn brann- og eksplosjonsvernloven § 13 (lov); brannvesenets tilsynsoppgave § 11 (lov); eierens systematiske sikkerhetsarbeid forskrift om brannforebygging § 9 og risikobasert tilsyn § 18 (forskrift).
STATUTE: The municipality supervises 'special fire objects' -- buildings, areas and undertakings where a fire could cause loss of many lives or major harm to health, environment or property. For such objects the owner and operator must have organised fire safety through systematic safety work with a responsible person, and deficiencies found at the fire inspection must be closed within the deadline. Legal basis: special fire objects and municipal supervision Fire and Explosion Protection Act §13 (statute); fire service supervision §11 (statute); owner's systematic safety work Fire Prevention Regulation §9 and risk-based inspection §18 (regulation).
Checks on this requirement
- For a special fire object: is fire safety organised with a responsible person, and are deficiencies from the fire inspection closed within the deadline?
Brann- og eksplosjonsvernloven (LOV-2002-06-14-20) § 5 (alminnelig aktsomhet) og § 6; forskrift om elektriske lavspenningsanlegg (FEL); NEK 400 (elektriske lavspenningsinstallasjoner)
LOV: Enhver plikter å vise alminnelig aktsomhet slik at brann ikke oppstår, og eier skal holde elektriske installasjoner og varmeproduserende utstyr i forsvarlig stand slik at de ikke utgjør en tennkilde (ingen overbelastning, overoppheting eller provisoriske/uautoriserte koblinger). Elektriske anlegg skal være utført og vedlikeholdt i samsvar med NEK 400, og ettersyn/termografi brukes for å avdekke varmgang. Rettsgrunnlag: alminnelig aktsomhet brann- og eksplosjonsvernloven § 5 (lov); eierens vedlikehold § 6 (lov); utførelse og tilstand NEK 400 (standard).
STATUTE: Everyone must exercise ordinary care so that fire does not arise, and the owner must keep electrical installations and heat-producing equipment in sound condition so they do not form an ignition source (no overload, overheating or makeshift/unauthorised connections). Electrical systems must be executed and maintained in accordance with NEK 400, and inspection/thermography used to reveal hot spots. Legal basis: ordinary care Fire and Explosion Protection Act §5 (statute); owner's maintenance §6 (statute); execution and condition NEK 400 (standard).
Checks on this requirement
- Are electrical installations and heat-producing equipment in sound condition (no overload, hot spots or makeshift connections) and kept clear of combustibles?
Brann- og eksplosjonsvernloven (LOV-2002-06-14-20) § 5 og kapittel 4 (håndtering av farlig stoff); forskrift om håndtering av farlig stoff (FOR-2009-06-08-602)
LOV: Brannfarlig, reaksjonsfarlig og trykksatt stoff (brannfarlig væske og gass, herunder gassflasker) skal oppbevares og håndteres på avsatte, ventilerte og sikrede steder, i tillatte mengder, atskilt fra tennkilder og rømningsveier. Håndtering ut over mindre mengder kan være meldepliktig til myndighetene. Rettsgrunnlag: aktsomhet brann- og eksplosjonsvernloven § 5 (lov); krav til håndtering av farlig stoff loven kapittel 4 og forskrift om håndtering av farlig stoff (forskrift).
STATUTE: Flammable, reactive and pressurised substances (flammable liquids and gases, incl. gas cylinders) must be stored and handled in designated, ventilated and secured places, in permitted quantities, separated from ignition sources and escape routes. Handling beyond minor quantities may require notification to the authorities. Legal basis: care Fire and Explosion Protection Act §5 (statute); handling of dangerous substances Act Chapter 4 and Regulation on handling of dangerous substances (regulation).
Checks on this requirement
- Are flammable liquids and gas (cylinders) stored in a designated, ventilated place in the permitted quantity, separated from ignition sources and escape routes?
Byggteknisk forskrift TEK17 (FOR-2017-06-19-840) kap. 11 (seksjonering, brannceller, bæreevne ved brann); forskrift om brannforebygging (FOR-2015-12-17-1710) § 5 (vedlikehold av bygningsdeler); EN 13501 (materialers branntekniske klasser)
FORSKRIFT: Branncellebegrensende og seksjoneringsbegrensende bygningsdeler (brannskiller, etasjeskillere) med tilhørende tettinger av gjennomføringer, branndører og brannspjeld skal holdes hele og uten utette åpninger; brannmotstanden til bærende og skillende konstruksjoner skal opprettholdes, og benyttede materialer skal oppfylle foreskreven brannteknisk klasse. Rettsgrunnlag: seksjonering og brannmotstand byggteknisk forskrift TEK17 kap. 11 (forskrift); vedlikehold av bygningsdeler forskrift om brannforebygging § 5 (forskrift); materialklasser EN 13501 (standard).
REGULATION: Fire-compartment and section-limiting building parts (fire separations, floor separations) with their penetration seals, fire doors and fire dampers must be kept intact and free of unsealed openings; the fire resistance of load-bearing and separating structures must be preserved, and materials used must meet the prescribed fire class. Legal basis: compartmentation and fire resistance Building Technical Regulation TEK17 ch. 11 (regulation); maintenance of building parts Fire Prevention Regulation §5 (regulation); material classes EN 13501 (standard).
Checks on this requirement
- Are fire-compartment/section separations intact, penetrations sealed and fire doors/dampers functional (no open, unsealed penetrations)?
- Is the fire resistance of load-bearing/separating structures preserved, and do fire doors self-close with adequate fire class?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 11 (brannsikker bruk - framkommelighet i rømningsveier); byggteknisk forskrift TEK17 (FOR-2017-06-19-840) kap. 11 (rømning og redning)
FORSKRIFT: Rømningsveier og adkomsten til dem skal holdes frie for hindringer og ha tilstrekkelig framkommelighet slik at personer kan rømme raskt og sikkert; det skal ikke lagres gjenstander eller brennbart materiale i rømningsveier. Dører i rømningsvei skal kunne åpnes lett og uten nøkkel, i rømningsretningen der det kreves, og slagretning og beslag skal være i orden. Rettsgrunnlag: framkommelighet i rømningsveier forskrift om brannforebygging § 11 (forskrift); utforming av rømningsveier og dører byggteknisk forskrift TEK17 kap. 11 (forskrift).
REGULATION: Escape routes and the access to them must be kept free of obstructions and have adequate passability so that people can escape quickly and safely; no goods or combustible material may be stored in escape routes. Doors in an escape route must open easily and without a key, in the escape direction where required, with swing direction and hardware in order. Legal basis: passability of escape routes Fire Prevention Regulation §11 (regulation); design of escape routes and doors Building Technical Regulation TEK17 ch. 11 (regulation).
Checks on this requirement
- Do doors in an escape route open easily without a key (working panic/emergency hardware where required), and swing the correct way?
- Are the escape routes free of obstructions and stored material, with adequate passability throughout?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 11 (brannsikker bruk av byggverk) og § 12 (brukerens systematiske sikkerhetsarbeid); brann- og eksplosjonsvernloven (LOV-2002-06-14-20) § 8 (systematisk helse-, miljø- og sikkerhetsarbeid)
FORSKRIFT: Den som bruker byggverket (virksomheten) skal sørge for at byggverket brukes i samsvar med kravene til brannsikkerhet, at rømningsveiene har tilstrekkelig framkommelighet, og at feil og mangler som kan påvirke brannsikkerheten meldes til eier. Virksomheten skal arbeide systematisk med sikkerheten, herunder gi ansatte tilstrekkelig opplæring i brannsikkerhet og gjennomføre rømnings- og beredskapsøvelser tilpasset risikoen. Rettsgrunnlag: brannsikker bruk forskrift om brannforebygging § 11 (forskrift); brukerens systematiske sikkerhetsarbeid § 12 (forskrift); virksomhetens internkontroll brann- og eksplosjonsvernloven § 8 (lov).
REGULATION: The user of the building (the undertaking) must ensure the building is used in accordance with the fire-safety requirements, that escape routes have adequate passability, and that faults and deficiencies affecting fire safety are reported to the owner. The undertaking must work systematically on safety, including giving staff adequate fire-safety training and holding evacuation and emergency drills appropriate to the risk. Legal basis: fire-safe use Fire Prevention Regulation §11 (regulation); user's systematic safety work §12 (regulation); undertaking's internal control Fire and Explosion Protection Act §8 (statute).
Checks on this requirement
- Is the building used in line with its fire-safety assumptions (occupant load, furnishings, escape routes), and are faults reported to the owner?
- Have staff received fire-safety training, and are evacuation/emergency drills held appropriate to the risk?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 4 (kunnskap og informasjon om brannsikkerhet i byggverk) og § 10 (eierens dokumentasjon); brann- og eksplosjonsvernloven (LOV-2002-06-14-20) § 6 (forebyggende sikringstiltak og vedlikehold)
FORSKRIFT: Eier av byggverk skal kjenne kravene til brannsikkerhet som gjelder for byggverket og ha kunnskap om de bygningsdelene, installasjonene og det utstyret som skal oppdage brann eller begrense konsekvensene av en brann. Eier skal informere brukerne om kravene som gjelder og om egenskaper ved byggverket som har betydning for brannsikkerheten. Eier skal ha dokumentasjon som viser at pliktene etter forskriften er oppfylt (branndokumentasjon) og gjøre den tilgjengelig ved tilsyn. Rettsgrunnlag: kunnskap og informasjon forskrift om brannforebygging § 4 (forskrift); eierens dokumentasjon § 10 (forskrift); eierens vedlikeholdsplikt brann- og eksplosjonsvernloven § 6 (lov).
REGULATION: The building owner must know the fire-safety requirements applying to the building and have knowledge of the building parts, installations and equipment intended to detect fire or limit the consequences of a fire. The owner must inform users of the applicable requirements and of the building's fire-safety-relevant properties. The owner must hold documentation showing that the duties under the regulation are met (fire-safety documentation) and make it available at inspection. Legal basis: knowledge and information Fire Prevention Regulation §4 (regulation); owner's documentation §10 (regulation); owner's maintenance duty Fire and Explosion Protection Act §6 (statute).
Checks on this requirement
- Does the owner know the building's fire-safety requirements, and is up-to-date fire-safety documentation available at inspection?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 5 (kontroll og vedlikehold av bygningsdeler og sikkerhetsinnretninger); brann- og eksplosjonsvernloven (LOV-2002-06-14-20) § 6
FORSKRIFT: Eier skal sørge for at bygningsdeler, installasjoner og sikkerhetsinnretninger som skal oppdage brann, varsle, lette rømning og redning eller begrense spredning av brann og røyk, blir kontrollert og vedlikeholdt slik at de virker etter hensikten. Kontroll og vedlikehold skal gjennomføres i samsvar med leverandørens anvisninger og relevante standarder, og skal dokumenteres. Rettsgrunnlag: kontroll og vedlikehold forskrift om brannforebygging § 5 (forskrift); eierens vedlikeholdsplikt brann- og eksplosjonsvernloven § 6 (lov).
REGULATION: The owner must ensure that building parts, installations and safety devices intended to detect fire, alarm, ease escape and rescue, or limit the spread of fire and smoke, are inspected and maintained so they function as intended. Inspection and maintenance must follow the supplier's instructions and relevant standards and be documented. Legal basis: inspection and maintenance Fire Prevention Regulation §5 (regulation); owner's maintenance duty Fire and Explosion Protection Act §6 (statute).
Checks on this requirement
- Are the fire and safety installations (alarm, extinguishing, smoke control, escape) inspected and maintained per the supplier's instructions and documented?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 5 (kontroll og vedlikehold av sikkerhetsinnretninger); byggteknisk forskrift TEK17 (FOR-2017-06-19-840) kap. 11; NS-EN 12101 (røyk- og varmekontrollsystemer)
FORSKRIFT: Der det er installert røykventilasjon (røyk- og varmekontroll), skal anlegget som sikkerhetsinnretning holdes i funksjonsdyktig stand og vedlikeholdes med jevne mellomrom (røykluker/røykvinduer og vifter virker ved prøve, røyk- og erstatningsluftåpninger frie, styring og sikret strømforsyning i orden). Rettsgrunnlag: kontroll og vedlikehold forskrift om brannforebygging § 5 (forskrift); utførelse og prøver NS-EN 12101 (standard).
REGULATION: Where a smoke ventilation (smoke and heat control) system is installed, as a safety device it must be kept operational and maintained at intervals (smoke hatches/windows and fans operate on test, smoke-exhaust and make-up air openings clear, control and backed-up power supply in order). Legal basis: inspection and maintenance Fire Prevention Regulation §5 (regulation); execution and tests NS-EN 12101 (standard).
Checks on this requirement
- Does the smoke ventilation operate on test (hatches/windows/fans open/start), are the smoke-exhaust and make-up air openings clear, and is the system maintained?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 5 (kontroll og vedlikehold av sikkerhetsinnretninger); byggteknisk forskrift TEK17 (FOR-2017-06-19-840) kap. 11; NS-EN 12845 (faste brannslokkesystemer - sprinklersystemer) og NS-EN 15004 (gasslokkeanlegg)
FORSKRIFT: Der det er installert et automatisk slokkeanlegg (sprinkler-, gass-, skum- eller vanntåkeanlegg), skal anlegget som sikkerhetsinnretning være i beredskaps- og funksjonsdyktig stand (trykksatt, ventiler åpne/overvåket, dyser/sprinklerhoder frie, vann-/slokkemiddelkilde og pumper i orden) og kontrolleres og vedlikeholdes med jevne mellomrom. Rettsgrunnlag: kontroll og vedlikehold forskrift om brannforebygging § 5 (forskrift); prosjektering og vedlikehold NS-EN 12845 (standard).
REGULATION: Where an automatic extinguishing system (sprinkler, gas, foam or water-mist) is installed, as a safety device it must be in a standby, operational state (pressurised, valves open/monitored, nozzles/sprinkler heads clear, water/agent source and pumps in order) and inspected and maintained at intervals. Legal basis: inspection and maintenance Fire Prevention Regulation §5 (regulation); design and maintenance NS-EN 12845 (standard).
Checks on this requirement
- Is the automatic extinguishing system in standby (pressurised, valves open/monitored, nozzles clear, water source/pumps in order) and inspected/maintained regularly?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 5 (kontroll og vedlikehold av sikkerhetsinnretninger); byggteknisk forskrift TEK17 (FOR-2017-06-19-840) § 11-12; NS 3960:2019 (brannalarmanlegg - prosjektering, installasjon, drift og vedlikehold) og NS-EN 54 (komponenter)
FORSKRIFT + STANDARD: Der det kreves, skal byggverket ha et brannalarmanlegg som pålitelig oppdager og varsler brann; som sikkerhetsinnretning skal anlegget holdes i funksjonsdyktig stand og kontrolleres og vedlikeholdes jevnlig (sentral uten feil, detektorer virksomme, varsling hørbar/synlig). Rettsgrunnlag: kontroll og vedlikehold forskrift om brannforebygging § 5 (forskrift); krav om brannalarm byggteknisk forskrift TEK17 § 11-12 (forskrift); prosjektering, drift og vedlikehold NS 3960 og komponenter NS-EN 54 (standard).
REGULATION + STANDARD: Where required, the building must have a fire alarm system that reliably detects and signals fire; as a safety device it must be kept operational and inspected and maintained regularly (panel without fault, detectors active, alarm audible/visible). Legal basis: inspection and maintenance Fire Prevention Regulation §5 (regulation); fire-alarm requirement Building Technical Regulation TEK17 §11-12 (regulation); design, operation and maintenance NS 3960 and components NS-EN 54 (standard).
Checks on this requirement
- Is the fire alarm system operational (panel without fault, detectors active, alarm audible) and inspected/maintained regularly?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 5 (kontroll og vedlikehold); byggteknisk forskrift TEK17 (FOR-2017-06-19-840) kap. 11 (slokkeutstyr); NS-EN 671-1/-2 (brannslangetromler og brannslanger) og NS-EN 671-3 (vedlikehold)
FORSKRIFT + STANDARD: Der det kreves, skal byggverket ha brannslanger/brannslangetromler for førstehjelpsslokking med tilstrekkelig trykk og vannmengde, plassert lett tilgjengelig; som sikkerhetsinnretning skal de holdes i funksjonsdyktig stand og vedlikeholdes, og slangene trykkprøves med jevne mellomrom. Rettsgrunnlag: kontroll og vedlikehold forskrift om brannforebygging § 5 (forskrift); krav til slokkeutstyr byggteknisk forskrift TEK17 (forskrift); utførelse og vedlikehold NS-EN 671 (standard).
REGULATION + STANDARD: Where required, the building must have hose reels/fire hoses for first-aid firefighting at adequate pressure and flow, placed readily accessible; as a safety device they must be kept operational and maintained, and the hoses pressure-tested at intervals. Legal basis: inspection and maintenance Fire Prevention Regulation §5 (regulation); extinguishing-equipment requirements Building Technical Regulation TEK17 (regulation); execution and maintenance NS-EN 671 (standard).
Checks on this requirement
- Are hose reels provided where required, at adequate pressure/flow, readily accessible and maintained (annual check, periodic pressure test)?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 5 (kontroll og vedlikehold); byggteknisk forskrift TEK17 (FOR-2017-06-19-840) § 11-12; NS 3926-1:2017 (visuelle ledesystemer for rømning) og NS-EN 1838 / NEK-EN 50172 (nødlys/ledelys)
FORSKRIFT + STANDARD: Der det kreves, skal rømningsveiene ha nødlys (ledelys) og eventuelt visuelt ledesystem som slår seg på automatisk ved bortfall av normal strømforsyning og lyser opp rømningsveien i foreskrevet tid; som sikkerhetsinnretning skal nødlyset kontrolleres og vedlikeholdes jevnlig. Rettsgrunnlag: kontroll og vedlikehold forskrift om brannforebygging § 5 (forskrift); krav om nødlys/ledesystem byggteknisk forskrift TEK17 § 11-12 (forskrift); ledesystem NS 3926-1 og belysningsstyrke/varighet NS-EN 1838 og NEK-EN 50172 (standard).
REGULATION + STANDARD: Where required, escape routes must have emergency (guidance) lighting and possibly a visual guidance system that switches on automatically on loss of normal power supply and illuminates the escape route for the prescribed time; as a safety device the emergency lighting must be inspected and maintained regularly. Legal basis: inspection and maintenance Fire Prevention Regulation §5 (regulation); requirement for emergency lighting/guidance Building Technical Regulation TEK17 §11-12 (regulation); guidance system NS 3926-1 and illuminance/duration NS-EN 1838 and NEK-EN 50172 (standard).
Checks on this requirement
- Does the emergency lighting/guidance system activate on power loss, illuminate the escape route for the required time, and has it been inspected and function-tested?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 5 (vedlikehold av sikkerhetsinnretninger); byggteknisk forskrift TEK17 (FOR-2017-06-19-840) § 11-12 (tiltak for å påvirke rømnings- og redningstider); NS 3926-1:2017 (visuelle ledesystemer for rømning); NS-EN ISO 7010 (sikkerhetsskilt)
FORSKRIFT + STANDARD: Der det kreves, skal rømningsveiene være merket med tydelige og varige rømnings- og henvisningsskilt, herunder retningsskilt der utgangen ikke er direkte synlig. Skiltene skal være hele, synlige og i samsvar med standard. Rettsgrunnlag: merking og vedlikehold av sikkerhetsinnretninger forskrift om brannforebygging § 5 (forskrift); krav til merking byggteknisk forskrift TEK17 § 11-12 (forskrift); utforming av ledesystem NS 3926-1 og skiltsymboler NS-EN ISO 7010 (standard).
REGULATION + STANDARD: Where required, escape routes must be marked with clear and durable exit and directional signs, incl. directional signs where the exit is not directly visible. Signs must be intact, visible and standard-compliant. Legal basis: marking and maintenance of safety devices Fire Prevention Regulation §5 (regulation); marking requirements Building Technical Regulation TEK17 §11-12 (regulation); guidance-system design NS 3926-1 and sign symbols NS-EN ISO 7010 (standard).
Checks on this requirement
- Are escape routes marked with intact, visible exit and directional signs, including where the exit is not directly visible?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 6 (eierens kontroll og vedlikehold av fyringsanlegg) og § 17 (kommunens feiing og tilsyn med fyringsanlegg)
FORSKRIFT: Eier av byggverk med fyringsanlegg skal sørge for at røykkanaler, skorstein og ildsted er i forsvarlig stand, melde fra til kommunen om nytt eller vesentlig endret fyringsanlegg, og gjøre anlegget tilgjengelig for feiing og tilsyn. Kommunen skal sørge for at det gjennomføres feiing og tilsyn med fyringsanlegg etter behov, med intervaller fastsatt ut fra risiko. Rettsgrunnlag: eierens plikt for fyringsanlegg forskrift om brannforebygging § 6 (forskrift); feiing og tilsyn med fyringsanlegg § 17 (forskrift).
REGULATION: The owner of a building with a heating appliance must ensure that flues, chimney and hearth are in sound condition, notify the municipality of a new or substantially altered heating appliance, and make the installation accessible for sweeping and inspection. The municipality must ensure that sweeping and inspection of heating appliances are carried out as needed, at intervals set on a risk basis. Legal basis: owner's duty for heating appliance Fire Prevention Regulation §6 (regulation); sweeping and inspection of heating appliances §17 (regulation).
Checks on this requirement
- Is the heating appliance (chimney, flues, hearth) in sound condition, accessible for sweeping, and has need-based sweeping/inspection been carried out?
Forskrift om brannforebygging (FOR-2015-12-17-1710) § 7 (brannvarsling og manuelt slokkeutstyr i bolig og fritidsbolig) og § 5 (kontroll og vedlikehold); NS 3910:2020 (vedlikehold av håndslokkere); NS-EN 3 (håndslokkere)
FORSKRIFT + STANDARD: Der det kreves, skal byggverket ha et tilstrekkelig antall håndslokkere (brannslokkeapparat) av riktig type i forhold til brannrisikoen, godt synlig og lett tilgjengelig; i bolig og fritidsbolig kreves manuelt slokkeutstyr etter § 7. Håndslokkere skal kontrolleres årlig og gjennomgå utvidet kontroll/service i samsvar med NS 3910. Rettsgrunnlag: manuelt slokkeutstyr i bolig forskrift om brannforebygging § 7 og vedlikehold av sikkerhetsinnretninger § 5 (forskrift); vedlikehold av håndslokkere NS 3910:2020 og krav til apparatene NS-EN 3 (standard).
REGULATION + STANDARD: Where required, the building must have a sufficient number of the correct type of portable extinguishers for the fire risk, clearly visible and readily accessible; in dwellings and holiday homes manual extinguishing equipment is required under §7. Extinguishers must be checked annually and undergo extended control/service in accordance with NS 3910. Legal basis: manual extinguishing equipment in dwellings Fire Prevention Regulation §7 and maintenance of safety devices §5 (regulation); maintenance of extinguishers NS 3910:2020 and extinguisher requirements NS-EN 3 (standard).
Checks on this requirement
- Are there enough extinguishers of the correct type, readily accessible, with a valid annual inspection and service per NS 3910?
FireCite is in beta: all 33 jurisdictions are expert-verified and shown as preview, not yet legally authoritative for compliance use.
FireCite summarises published law and standards; it is not legal advice and not a substitute for a competent fire risk assessor or the authority having jurisdiction. Regulation changes: every citation carries the edition it was checked against.