Fire safety inspection requirements in Slovenia
What a fire inspection has to cover in Slovenia — the instruments that impose it, and the clause each check is cited to.
1 instrument · 16 requirements · 18 checks · authoritative language: SL
Requirements below are shown in SL — the legally authoritative language in Slovenija — with an English translation beneath. The translation is a convenience and is never the requirement itself.
The instruments we cite
Zakon o varstvu pred pozarom (ZVPoz, Ur. l. RS 3/07-UPB1, 9/11, 83/12, 61/17 - GZ, 189/20 - ZFRO, 43/22 -- obveznosti lastnika oz. uporabnik · edition Zakon o varstvu pred pozarom (ZVPoz; uradno precisceno besedilo Ur. l. RS 3/07-UPB1, spremembe 9/11, 83/12, 61/17 - GZ, 189/20 - ZFRO in 43/22), veljavno besedilo; Pravilnik o pozarnem redu (Ur. l. RS 52/07, 34/11, 101/11), veljavno besedilo; Pravilnik o pozarni varnosti v stavbah (Ur. l. RS 31/04, 10/05, 83/05, 14/07, 61/17 - GZ; 9., 11., 12., del 13. in 14. clen ter Prilogi 1 in 3 razveljavljeni s Pravilnikom o zasnovi in studiji pozarne varnosti, Ur. l. RS 12/13, 11. clen) in Tehnicna smernica TSG-1-001:2019 'Pozarna varnost v stavbah'; Pravilnik o nadzoru vgrajenih sistemov aktivne pozarne zascite (Ur. l. RS 53/19); Pravilnik o izbiri in namestitvi gasilnih aparatov (Ur. l. RS 67/05) in Pravilnik o minimalnih tehnicnih in drugih pogojih za vzdrzevanje rocnih in prevoznih gasilnih aparatov (Ur. l. RS 108/04, 116/07, 102/09, 55/15); Pravilnik o tehnicnih normativih za hidrantno omrezje za gasenje pozarov (veljavno besedilo, nazadnje spremenjeno z Ur. l. RS 199/21) in Pravilnik o preizkusanju hidrantnih omrezij; standardi SIST EN v veljavnih izdajah (SIST EN 3, SIST EN 671, SIST EN 1838, SIST EN 50172, SIST EN 54, SIST EN 12845, SIST EN 12101, SIST EN ISO 7010, SIST EN 13501) ter nacionalni standard SIST 1013 (oznacevanje mesta gasilnika)
What an inspection covers
Pravilnik o izbiri in namestitvi gasilnih aparatov (Ur. l. RS 67/05) -- izbira, namestitev in označitev mesta gasilnika (SIST 1013); Pravilnik o minimalnih tehničnih in drugih pogojih za vzdrževanje ročnih in prevoznih gasilnih aparatov (Ur. l. RS 108/04, 116/07, 102/09, 55/15) -- servisno vzdrževanje po navodilih proizvajalca; SIST EN 3 (gasilniki)
PRAVILNIK + STANDARD: V objektu je treba zagotoviti zadostno število primernih gasilnih aparatov glede na namembnost in požarno ogroženost prostorov, na dobro vidnih in lahko dostopnih mestih, mesto gasilnika pa označiti v skladu s standardom SIST 1013. Gasilniki morajo biti brezhibni in servisno vzdrževani PO NAVODILIH PROIZVAJALCA -- pravilnik ne določa enotnega statutarnega roka (npr. letnega); datum naslednjega servisa je razviden iz nalepke oziroma plombe serviserja na gasilniku. Pravna podlaga: izbira, namestitev in označitev mesta gasilnika Pravilnik o izbiri in namestitvi gasilnih aparatov in SIST 1013 (pravilnik + standard); servisno vzdrževanje po navodilih proizvajalca Pravilnik o minimalnih tehničnih in drugih pogojih za vzdrževanje ročnih in prevoznih gasilnih aparatov (pravilnik); zahteve za gasilnike SIST EN 3 (standard).
REGULATION + STANDARD: A sufficient number of suitable fire extinguishers must be provided for the premises' use and fire risk, in clearly visible and readily accessible places, and the extinguisher's location marked to standard SIST 1013 (Slovenia's own national marking standard -- NOT SIST EN ISO 7010). Extinguishers must be sound and serviced PER MANUFACTURER INSTRUCTIONS -- the pravilnik sets no single statutory interval (e.g. no fixed annual cadence); the next-service due date is shown on the servicer's label/seal on the extinguisher itself. Legal basis: selection, installation and marking Rules on Selection and Installation of Fire Extinguishers and SIST 1013 (regulation + standard); manufacturer-instruction maintenance Rules on Minimum Conditions for Maintenance of Portable and Mobile Fire Extinguishers (regulation); extinguisher requirements SIST EN 3 (standard).
Checks on this requirement
- Are enough suitable extinguishers provided, readily accessible, with the location marked to SIST 1013, and serviced per manufacturer instructions (per the date on the label/seal)?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) -- obvladovanje virov vžiga in raba električnih instalacij; Zakon o varstvu pred požarom -- splošne obveznosti
PRAVILNIK: Električne instalacije in naprave morajo biti tehnično brezhibne in uporabljene skladno z zahtevami, da ne postanejo vir vžiga (prepovedani so preobremenitve, začasne ali poškodovane instalacije, hranjenje gorljivih materialov ob segretih površinah); vire vžiga je treba obvladovati, znane pomanjkljivosti pa odpraviti. Pravna podlaga: obvladovanje virov vžiga in raba električnih instalacij Pravilnik o požarnem redu (pravilnik); splošne obveznosti Zakon o varstvu pred požarom (zakon).
REGULATION: Electrical installations and appliances must be technically sound and used per requirements so they do not become an ignition source (no overload, temporary or damaged wiring, or combustibles stored near heated surfaces); ignition sources must be controlled and known faults remedied. Legal basis: control of ignition sources and use of electrical installations Rules on the Fire Order (regulation); general duties Fire Protection Act (statute).
Checks on this requirement
- Are electrical installations sound (no overload, overheating or temporary wiring) and are combustibles kept away from ignition sources?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) -- označevanje evakuacijskih poti in varnostni znaki; SIST EN ISO 7010 (varnostni znaki)
PRAVILNIK + STANDARD: Kjer je določeno, morajo biti evakuacijske poti in izhodi označeni z jasnimi in obstojnimi evakuacijskimi (varnostnimi) znaki, vključno s smernimi znaki tam, kjer izhod ni neposredno viden; znaki morajo biti nepoškodovani, vidni in skladni s standardom. Pravna podlaga: označevanje evakuacijskih poti in varnostni znaki Pravilnik o požarnem redu (pravilnik); simboli znakov SIST EN ISO 7010 (standard).
REGULATION + STANDARD: Where prescribed, escape routes and exits must be marked with clear and durable evacuation (safety) signs, including directional signs where the exit is not directly visible; signs must be intact, visible and standard-compliant. Legal basis: escape-route marking and safety signs Rules on the Fire Order (regulation); sign symbols SIST EN ISO 7010 (standard).
Checks on this requirement
- Are escape routes marked with intact, visible evacuation and directional signs, including where the exit is not directly visible?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) -- požarni načrt in načrt evakuacije ter njuna namestitev
PRAVILNIK: Za objekte določene namembnosti in zasedenosti je treba izdelati požarni načrt in načrt evakuacije ter načrt evakuacije izobesiti na vidnih mestih; načrt prikazuje evakuacijske poti, izhode, mesta opreme za gašenje in ravnanje ob požaru ter mora ustrezati dejanski razporeditvi prostorov in biti razumljiv. Pravna podlaga: požarni načrt in načrt evakuacije Pravilnik o požarnem redu (pravilnik).
REGULATION: For buildings of prescribed use and occupancy a fire plan and an evacuation plan must be prepared, and the evacuation plan posted in visible places; the plan shows escape routes, exits, locations of firefighting equipment and conduct in case of fire, and must match the actual layout and be understandable. Legal basis: fire plan and evacuation plan Rules on the Fire Order (regulation).
Checks on this requirement
- Are the fire plan and evacuation plan prepared, and is the evacuation plan posted in visible places and matching the actual layout?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) -- požarni red in odgovorna oseba za varstvo pred požarom; Zakon o varstvu pred požarom (ZVPoz, Ur. l. RS 3/07-UPB1, 9/11, 83/12, 61/17 - GZ, 189/20 - ZFRO, 43/22) -- obveznosti lastnika oz. uporabnika objekta
PRAVILNIK: Lastnik ali uporabnik objekta mora izdelati in sprejeti požarni red, ki ustreza namembnosti in požarni ogroženosti objekta, ter določiti odgovorno osebo za izvajanje ukrepov varstva pred požarom. Požarni red določa organizacijo varstva pred požarom, ukrepe varstva pred požarom, dolžnosti zaposlenih in obiskovalcev ter ravnanje ob požaru; biti mora ažuren in dostopen ob inšpekcijskem nadzoru. Pravna podlaga: požarni red in odgovorna oseba Pravilnik o požarnem redu (pravilnik); obveznosti lastnika oz. uporabnika Zakon o varstvu pred požarom (zakon).
REGULATION: The owner or user of the building must draw up and adopt a fire order (pozarni red) appropriate to the building's use and fire risk, and appoint a person responsible for fire-safety measures. The fire order sets the fire-safety organisation, fire-safety measures, duties of staff and visitors, and conduct in case of fire; it must be current and available at an inspection. Legal basis: fire order and responsible person Rules on the Fire Order (regulation); owner/user duties Fire Protection Act (statute).
Checks on this requirement
- Does the building have a current, adopted fire order and an appointed person responsible for fire safety?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) -- prosta prehodnost evakuacijskih poti; Pravilnik o požarni varnosti v stavbah (Ur. l. RS 31/04, 10/05, 83/05, 14/07, 61/17 - GZ; deloma razveljavljen s Pravilnikom o zasnovi in študiji požarne varnosti, Ur. l. RS 12/13) in TSG-1-001:2019 -- evakuacijske poti in vrata
PRAVILNIK + TSG: Evakuacijske poti, izhodi in dostopi do njih morajo biti stalno prosti, neovirani s predmeti ali gorljivimi materiali in zadostne prepustnosti, da se ljudje lahko hitro in varno evakuirajo. Vrata na evakuacijskih izhodih se morajo z notranje strani zlahka odpreti brez ključa in se, kjer je določeno, odpirati v smeri evakuacije. Pravna podlaga: prosta prehodnost evakuacijskih poti Pravilnik o požarnem redu (pravilnik); zahteve za evakuacijske poti in vrata Pravilnik o požarni varnosti v stavbah in TSG-1-001:2019 (pravilnik + tehnična smernica).
REGULATION + TSG: Escape routes, exits and their approaches must be kept clear at all times, unobstructed by objects or combustibles, and of adequate capacity so people can escape quickly and safely. Emergency exit doors must open easily from inside without a key and, where prescribed, open in the escape direction. Legal basis: clear escape routes Rules on the Fire Order (regulation); escape-route and door requirements Rules on Fire Safety in Buildings and TSG-1-001:2019 (regulation + technical guideline).
Checks on this requirement
- Do emergency exit doors open easily from inside without a key and swing the required way?
- Are escape routes and exits clear, unobstructed and of adequate capacity throughout?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) -- skladiščenje in raba vnetljivih (gorljivih) tekočin, plinov in plinskih jeklenk
PRAVILNIK: Vnetljive in nevarne snovi (gorljive tekočine, plini, plinske jeklenke) je treba hraniti na za to določenih, prezračevanih in zaščitenih mestih, v dovoljenih količinah, odmaknjeno od virov vžiga in evakuacijskih poti; skladiščenje in raba morata ustrezati predpisanim zahtevam. Pravna podlaga: skladiščenje vnetljivih in nevarnih snovi Pravilnik o požarnem redu (pravilnik).
REGULATION: Flammable and dangerous substances (flammable liquids, gases, gas cylinders) must be stored in designated, ventilated and protected places, in permitted quantities, away from ignition sources and escape routes; storage and use must meet the prescribed requirements. Legal basis: storage of flammable and dangerous substances Rules on the Fire Order (regulation).
Checks on this requirement
- Are flammable/dangerous substances and gas cylinders stored in a designated ventilated place, in the permitted quantity, away from ignition sources and escape routes?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) -- usposabljanje zaposlenih za varstvo pred požarom in praktične evakuacijske vaje; Zakon o varstvu pred požarom -- dolžnost usposabljanja
PRAVILNIK: Zaposlene je treba seznaniti in usposobiti za varstvo pred požarom (uvodno in obdobno usposabljanje), poznati morajo ravnanje ob požaru in postopek evakuacije; v določenih objektih je treba obdobno izvajati praktične evakuacijske vaje, usposabljanja in vaje pa dokumentirati (evidenca). Pravna podlaga: usposabljanje in evakuacijske vaje Pravilnik o požarnem redu (pravilnik); dolžnost usposabljanja Zakon o varstvu pred požarom (zakon).
REGULATION: Staff must be informed and trained in fire safety (induction and periodic training), must know the conduct in case of fire and the evacuation procedure; in prescribed buildings practical evacuation drills must be carried out periodically, and training and drills documented (records). Legal basis: training and evacuation drills Rules on the Fire Order (regulation); training duty Fire Protection Act (statute).
Checks on this requirement
- Have staff been trained in fire safety and are practical evacuation drills carried out (documented)?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) -- vzdrževanje sistema za javljanje požara; Pravilnik o nadzoru vgrajenih sistemov aktivne požarne zaščite (Ur. l. RS 53/19) -- obdobni pregled; SIST EN 54 (sestavni deli sistema)
PRAVILNIK + STANDARD: Kjer je določeno, mora biti v objektu vgrajen sistem za javljanje požara (samodejno javljanje požara), ki zanesljivo zazna požar in sproži alarm; kot vgrajeni sistem aktivne požarne zaščite mora biti delujoč ter obdobno pregledan in vzdrževan (centrala brez napak, javljalniki učinkoviti, alarm slišen/viden). Pravna podlaga: zahteva po sistemu za javljanje požara Pravilnik o požarnem redu (pravilnik); obdobni nadzor Pravilnik o nadzoru vgrajenih sistemov aktivne požarne zaščite (pravilnik); sestavni deli sistema SIST EN 54 (standard).
REGULATION + STANDARD: Where prescribed, the building must have a fire detection and alarm system (automatic fire detection) that reliably detects fire and triggers the alarm; as an installed active-fire-protection system it must be operational and periodically inspected and maintained (panel without faults, detectors effective, alarm audible/visible). Legal basis: fire detection requirement Rules on the Fire Order (regulation); periodic supervision Rules on Supervision of Installed Active Fire Protection Systems (regulation); system components SIST EN 54 (standard).
Checks on this requirement
- Is the fire detection and alarm system operational (panel without faults, detectors effective, alarm audible) and periodically inspected/maintained?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) -- zasilna (varnostna) razsvetljava; SIST EN 1838 / SIST EN 50172 (zasilna razsvetljava)
PRAVILNIK + STANDARD: Kjer je določeno, mora biti na evakuacijskih poteh vgrajena zasilna (varnostna) razsvetljava, ki se ob izpadu normalnega napajanja samodejno vklopi in osvetli evakuacijsko pot določeni čas; kot ukrep varstva pred požarom jo je treba obdobno preizkušati in vzdrževati. Pravna podlaga: zahteva po zasilni razsvetljavi Pravilnik o požarnem redu (pravilnik); raven osvetljenosti in čas delovanja SIST EN 1838 in SIST EN 50172 (standard).
REGULATION + STANDARD: Where prescribed, escape routes must have emergency (safety) lighting that switches on automatically on loss of normal power and illuminates the escape route for the set time; as a fire-safety measure it must be periodically tested and maintained. Legal basis: emergency-lighting requirement Rules on the Fire Order (regulation); illuminance and duration SIST EN 1838 and SIST EN 50172 (standard).
Checks on this requirement
- Does emergency lighting switch on when power fails, illuminate the route for the set time, and has it been tested?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) in Pravilnik o nadzoru vgrajenih sistemov aktivne požarne zaščite (Ur. l. RS 53/19) -- vzdrževanje sistema za odvod dima in toplote (SODT); SIST EN 12101 (odvod dima in toplote)
PRAVILNIK + STANDARD: Kjer je vgrajen sistem za odvod dima in toplote (SODT), mora biti kot vgrajeni sistem aktivne požarne zaščite vzdrževan in delujoč ter obdobno preizkušen (dimne lopute/okna in ventilatorji se ob preizkusu sprožijo, odvodne in dovodne (kompenzacijske) odprtine proste, krmiljenje in rezervno napajanje brezhibni). Pravna podlaga: vzdrževanje sistema za odvod dima in toplote Pravilnik o požarnem redu in Pravilnik o nadzoru vgrajenih sistemov aktivne požarne zaščite (pravilnik); elementi in preizkusi sistema SIST EN 12101 (standard).
REGULATION + STANDARD: Where a smoke and heat exhaust system (SODT) is installed, as an installed active-fire-protection system it must be maintained and operational and periodically tested (smoke hatches/windows and fans actuate on test, exhaust and make-up (compensating) openings clear, control and backup power sound). Legal basis: maintenance of smoke and heat exhaust system Rules on the Fire Order and Rules on Supervision of Installed Active Fire Protection Systems (regulation); system elements and tests SIST EN 12101 (standard).
Checks on this requirement
- Does the smoke and heat exhaust system actuate on test (hatches/windows/fans), are the exhaust and make-up openings clear, and is it maintained?
Pravilnik o požarnem redu (Ur. l. RS 52/07, 34/11, 101/11) in Pravilnik o nadzoru vgrajenih sistemov aktivne požarne zaščite (Ur. l. RS 53/19) -- vzdrževanje vgrajenega gasilnega sistema; SIST EN 12845 (sprinklerski sistemi)
PRAVILNIK + STANDARD: Kjer je vgrajen stabilni gasilni sistem (sprinklerski, plinski, penilni ali sistem vodne megle), mora biti kot vgrajeni sistem aktivne požarne zaščite v pripravljenosti in delujoč (napolnjen/pod tlakom, ventili odprti in nadzorovani, sprinklerske glave/razpršilniki prosti, vir vode ali gasilnega sredstva in črpalke brezhibni) ter obdobno pregledan in vzdrževan. Pravna podlaga: vzdrževanje vgrajenega gasilnega sistema Pravilnik o požarnem redu in Pravilnik o nadzoru vgrajenih sistemov aktivne požarne zaščite (pravilnik); projektiranje in vzdrževanje sistema SIST EN 12845 (standard).
REGULATION + STANDARD: Where a fixed extinguishing system (sprinkler, gas, foam or water-mist) is installed, as an installed active-fire-protection system it must be in a ready and operational state (charged/pressurised, valves open and monitored, sprinkler heads/nozzles clear, water or agent source and pumps sound) and periodically inspected and maintained. Legal basis: maintenance of fixed extinguishing system Rules on the Fire Order and Rules on Supervision of Installed Active Fire Protection Systems (regulation); system design and maintenance SIST EN 12845 (standard).
Checks on this requirement
- Is the fixed extinguishing system in a ready state (pressure, valves open/monitored, heads clear, water source/pumps sound) and periodically maintained?
Pravilnik o požarni varnosti v stavbah (Ur. l. RS 31/04, 10/05, 83/05, 14/07, 61/17 - GZ; deloma razveljavljen s Pravilnikom o zasnovi in študiji požarne varnosti, Ur. l. RS 12/13) in TSG-1-001:2019 -- požarni sektorji in požarna odpornost; Pravilnik o požarnem redu -- vzdrževanje; SIST EN 13501 (razvrščanje gradbenih proizvodov glede na odziv na ogenj)
PRAVILNIK + STANDARD: Ločeni in nosilni elementi požarnih sektorjev, požarne stene in stropovi z zatesnitvijo njihovih prehodov (prebojev), požarna vrata in požarne lopute morajo biti nepoškodovani, brez nezatesnjenih odprtin; požarna odpornost nosilnih in ločilnih konstrukcij mora biti ohranjena, uporabljeni gradbeni proizvodi pa morajo ustrezati predpisanemu razredu odziva na ogenj. Pravna podlaga: požarni sektorji in požarna odpornost Pravilnik o požarni varnosti v stavbah in TSG-1-001:2019 (pravilnik + tehnična smernica); vzdrževanje Pravilnik o požarnem redu (pravilnik); razvrščanje gradbenih proizvodov SIST EN 13501 (standard).
REGULATION + STANDARD: Separating and load-bearing elements of fire compartments, fire walls and floors with sealing of their penetrations, fire doors and fire dampers must be intact and free of unsealed openings; the fire resistance of load-bearing and separating structures must be preserved, and construction products used must meet the prescribed reaction-to-fire class. Legal basis: fire compartments and fire resistance Rules on Fire Safety in Buildings and TSG-1-001:2019 (regulation + technical guideline); maintenance Rules on the Fire Order (regulation); construction-product classification SIST EN 13501 (standard).
Checks on this requirement
- Is the fire resistance of load-bearing/separating structures preserved, and do fire doors self-close with the required fire resistance?
- Are fire walls/floors intact, penetrations sealed and fire dampers functional (no open, unsealed openings)?
Pravilnik o tehničnih normativih za hidrantno omrežje za gašenje požarov (Ur. l. RS 83/05, 199/21) -- notranje hidrantno omrežje; Pravilnik o preizkušanju hidrantnih omrežij -- obdobni preizkus; SIST EN 671 (hidrantna oprema s cevnimi koluti)
PRAVILNIK + STANDARD: Kjer je določeno, mora biti v objektu vgrajeno notranje hidrantno omrežje (notranji hidranti s cevnimi koluti) z zadostnim tlakom in količino vode za začetno gašenje, na lahko dostopnih mestih; kot ukrep varstva pred požarom mora biti brezhibno, vzdrževano in obdobno preizkušeno. Pravna podlaga: notranje hidrantno omrežje Pravilnik o tehničnih normativih za hidrantno omrežje za gašenje požarov (pravilnik); obdobni preizkus Pravilnik o preizkušanju hidrantnih omrežij (pravilnik); zahteve za hidrantno opremo SIST EN 671 (standard).
REGULATION + STANDARD: Where prescribed, the building must have an internal hydrant network (internal hydrants with hose reels) with adequate pressure and water flow for first-aid firefighting, in readily accessible places; as a fire-safety measure it must be sound, maintained and periodically tested. Legal basis: internal hydrant network Rules on Technical Norms for Fire-Fighting Hydrant Networks (regulation); periodic testing Rules on Testing of Hydrant Networks (regulation); hydrant-equipment requirements SIST EN 671 (standard).
Checks on this requirement
- Is the internal hydrant network provided where required, with adequate pressure/flow, readily accessible and periodically tested?
Pravilnik o tehničnih normativih za hidrantno omrežje za gašenje požarov (Ur. l. RS 83/05, 199/21) -- zunanje hidrantno omrežje in oskrba z vodo za gašenje; Pravilnik o požarnem redu -- vzdrževanje
PRAVILNIK: Zunanja oskrba z vodo za gašenje (zunanji hidranti, vodni zbiralniki ali odvzemna mesta), ki oskrbuje objekt, mora biti brezhibna, označena, dostopna gasilskim vozilom in zagotavljati potrebno količino vode za gašenje; hidranti se obdobno preizkušajo, pozimi pa se zaščitijo pred zmrzovanjem. Pravna podlaga: zunanje hidrantno omrežje in oskrba z vodo Pravilnik o tehničnih normativih za hidrantno omrežje za gašenje požarov (pravilnik); vzdrževanje Pravilnik o požarnem redu (pravilnik).
REGULATION: The external fire-water supply serving the building (external hydrants, water reservoirs or draw-off points) must be sound, marked, accessible to fire appliances and ensure the required water volume for firefighting; hydrants are periodically tested and, in winter, protected from freezing. Legal basis: external hydrant network and water supply Rules on Technical Norms for Fire-Fighting Hydrant Networks (regulation); maintenance Rules on the Fire Order (regulation).
Checks on this requirement
- Are external hydrants/draw-off points sound, marked, accessible and periodically tested (ensuring the required water volume)?
Zakon o varstvu pred požarom (ZVPoz, Ur. l. RS 3/07-UPB1, 9/11, 83/12, 61/17 - GZ, 189/20 - ZFRO, 43/22) -- inšpekcijski nadzor (Inšpektorat RS za varstvo pred naravnimi in drugimi nesrečami); Pravilnik o požarnem redu -- odprava ugotovljenih pomanjkljivosti
ZAKON: Nad izvajanjem ukrepov varstva pred požarom se izvaja inšpekcijski nadzor, ki ga opravlja Inšpektorat RS za varstvo pred naravnimi in drugimi nesrečami; pri nadzoru ugotovljene pomanjkljivosti (kršitve predpisov) je treba odpraviti v določenih rokih, izvedba pa mora biti dokumentirana. Pravna podlaga: inšpekcijski nadzor Zakon o varstvu pred požarom (zakon); odprava pomanjkljivosti Pravilnik o požarnem redu (pravilnik).
STATUTE: Fire-safety measures are subject to inspection carried out by the Inspectorate of the RS for Protection against Natural and Other Disasters; deficiencies (regulatory breaches) found at inspection must be remedied within the set deadlines and completion documented. Legal basis: inspection Fire Protection Act (statute); remedying deficiencies Rules on the Fire Order (regulation).
Checks on this requirement
- Have deficiencies found at an earlier inspection been remedied within the set deadlines and documented?